    针对直流微电网中异构电源动态差异大、固定功率分配难以兼顾母线电压调节与电源安全的问题,提出一种基于动态安全功率区间的多源协调控制方法。首先利用控制障碍函数(CBF)将各电源安全约束映射为状态相关的源侧安全功率区间,并综合变换器运行约束及功率跟踪误差,获得母线侧容许功率区间。其次基于母线电压控制李雅普诺夫函数(CLF)和鲁棒CBF分别构造电压调节约束与总注入功率安全约束,进而建立在线二次规划(QP),根据各支路安全裕量和动态响应特性协调分配功率。理论分析表明,在有界不确定性及离散采样影响下,所提控制策略可保证源侧与母线安全集的前向不变性,并使母线电压误差收敛至有界邻域。仿真结果表明,在负载阶跃、电源能力退化、聚合能力不足及负载估计误差工况下均未违反安全约束,可随安全功率区间变化自适应调整功率分配,并在供能不足时识别功率缺口并实施有界切负荷。

    Abstract:

    To address the difficulty of simultaneously achieving bus-voltage regulation and source-side safety in DC microgrids with heterogeneous power sources exhibiting significantly different dynamic characteristics, this paper proposes a multi-source coordinated control method based on dynamic safe power intervals. First, control barrier functions (CBFs) are employed to map the safety constraints of individual sources into state-dependent source-side safe power intervals. By further incorporating converter operating constraints and power-tracking errors, admissible bus-side power intervals are obtained. Subsequently, a bus-voltage control Lyapunov function (CLF) and robust CBFs are used to formulate the voltage-regulation constraint and the safety constraint on the total injected power, respectively. An online quadratic program (QP) is then established to coordinate power allocation according to the safety margins and dynamic response characteristics of individual branches. Theoretical analysis shows that, under bounded uncertainties and discrete-time sampling effects, the proposed control strategy guarantees the forward invariance of both the source-side and bus-side safe sets while ensuring that the bus-voltage error converges to a bounded neighborhood. Simulation results demonstrate that no safety constraints are violated under load steps, source-capability degradation, insufficient aggregate supply capability, and load-estimation errors. The proposed method adaptively reallocates power in response to variations in the safe power intervals and, under insufficient supply conditions, identifies the power deficit and performs bounded load shedding.

    参考文献
    相似文献
    引证文献
引用本文
相关视频

分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2026-08-25
  • 最后修改日期:2026-10-09
  • 录用日期:2026-10-10
  • 在线发布日期:
  • 出版日期:
文章二维码